Tags:
Eric,
I'm sure something could be figured out for that set up. Doing a CHOPS system though generally means the pump is feeding the fish tank which then overflows to the grow beds. To do an indexing valve in that situation (and it can be done as I have been doing it for my large system for well over a year now) you will need to an a low pressure automated valve to quickly start and stop flow between the fish tank and the indexing valve or some other means of doing that. I don't know that starting and stopping the pump flow to the fish tank would provide the flow and pressure needed quickly enough at the valve to provide smooth operation.
Most definitely an indexing valve can be used for a CHOPS system so long as you have ample flow and some height between the water level in the fish tank and the surface of the grow beds, plus an alternate path for overflow water to be filtered as well.
You ask if the valve would work with a 7900 gal/hr pump with a 4" discharge? I don't know that I would call that a low flow pump since that is providing a huge amount of water each minute. You might operate several indexing valves with such a pump, keep in mind the large indexing valves are only 1 1/2" fittings. You would definitely need an additional path for water to overflow from the fish tank since the water going through an indexing valve is not going to keep up with such an inflow to your fish tank.
I'm interested in the CHOP+indexing valve discussion as this is the setup I'm planning on. I was planning on using a pump in the sump on a timer that would pump to DWC tanks which would then all flow into the fish tank, which would then overflow into the indexing valve before being fed to the GBs and then the sump. The timer would provide the on/off required by the indexing valve, but now I'm not sure if the overflow from the fish tank (especially after already being split across multiple DWC tanks and then rejoined) will be strong and abrupt enough to trigger the valve. Do you think? I also want to have the GBs after the indexing valve at close to the same height as the water in the FT, just a little lower. It almost seems like I need to get a pressure valve or some automated valve before the indexing valve to deal with the slower initial trickle of the water in, but then why use the timer?
So I'm now thinking of going a slightly different route, instead I will let my pump run continuously (I'm planning on using the Laguna Max-Flo 1500; I called Laguna and the didn't recommend using on/off with a timer, they said if any debris gets into the well while it's off it won't start up again; so running this continuously is better anyway), so no timer on the pump, but instead of an indexing valve + automated valve I'm thinking of using a multiple-zone irrigation timer with electronic valves on a manifold, something like this (scroll down to see the package components): http://www.mrdrip.com/sprinklervalves.htm , using a timer like this (still need to look around more): http://www.teakwickerandmore.com/asp/show_detail.asp?sku=BHX1043 . What do you think of this? Are these the solenoid valves you mentioned would require your tank on the roof to work? I wonder if they can handle solids-filled water coming straight from the FT.. and I wonder about any exposed metals. I will have to call them for more info if you think this is something worth considering.
Thanks for any advice!
To operate the indexing valves, even the gravity modified ones, require a certain amount of flow and some pressure to function. The more tanks/beds you put between the inflow and the indexing valve, the more you slow down the action.
I do have an indexing valve running on my big system that is CHIFT PIST. The water level in the fish tank is about 18 inches above the surface of the grow beds. My pump runs constantly. To make this work I had to design a valve that I could automate that wouldn't require a differential pressure but would allow a huge flow through when opened so that I could get that good gush to engage the indexing valve properly. Here let me see if I can find my blog posts about it.
http://www.aquaponiclynx.com/low-pressure-automated-valve
As to the sprinkler type solenoids. The inexpensive ones like you linked to, they generally do require quite a bit of pressure to operate and they don't have big openings so you don't get much flow through unless it is under quite a bit of pressure. They will not work for gravity flow from a CHIFT situation. If you find some that do with an opening of more than 1" for less than $400, I'm interested.
Thanks TC, your advice is really appreciated. I had seen your automated valve before (impressive!), I guess I wasn't putting it all together though. Anyway thanks for the reality check.
I'm now thinking a better setup for me might be to adjust the flows so that I can connect the pump (on a timer again) directly to the indexing valve. On every flood cycle most of the water would go through the indexing valve, and then to a GB and back to the sump, but the other bit of water would go directly to the DWC tanks, then to the fish tank, then split across the GBs, then back to the sump, to keep some flow going through the FT. This is going to require more plumbing than before, but this way I can use a simple timer, pump & IV setup. I still need to estimate if I can get enough flow through the FT and also give the GBs enough time to drain the FT water that has been split to them, before the next one starts to fill. Sorry if this is confusing, it's hard to describe in text.
One issue though might be that one of the cycles I want from the indexing valve would be to feed a few towers. The indexing valve wouldn't need to be at the highest point of the plumbing, would it?
I was also wondering if the indexing valves have an option to connect polypipe directly to them, rather than PVC. I'm hoping to avoid PVC plumbing if I can.
Also, if I want to run my system on constant flood, can I simply take the mechanism out of the IV to open all of the outputs up, or will I need to design in a bypass for that situation?
Thanks!
you might look up the CHOP 2 design for more flexibility in your design.
I would suggest though that perhaps a separate pump feeding the fish tank and DWC to run constant and a pump on a timer feeding the grow beds might be easier. I like constant flow/aeration in my fish tank personally. If you are running a strong enough pump it is possible to have some of the flow going constantly to the fish tank and DWC beds while a solenoid valve could turn the flow on and off to an indexing valve feeding the grow beds. I have never done this type of install personally though and it would definitely take a stronger pump than my usually set up.
The indexing valve itself does not need to be the highest point, however if you are going to pull out the stem/disk to run constant flood, you need to have the outlets very even in order to get even flow out of them. If most are a grow bed height and one is up for towers, the one that is up won't get any flow when running without the stem disk unless your pump is huge.
The valves are designed for pvc pipes to fit into them. I don't know of any poly pipe that is the exact right size or if the glues would be compatible, I just don't know this. I would probably use a PVC street elbow and then adapt to a fitting that would work with the poly but, Small poly pipes will create lots of friction and reduce flows so I don't like to use them in my systems since I'm trying to get as much as possible from my pumps with the least amount of strain or energy usage.
Greener said:
Thanks TC, your advice is really appreciated. I had seen your automated valve before (impressive!), I guess I wasn't putting it all together though. Anyway thanks for the reality check.
I'm now thinking a better setup for me might be to adjust the flows so that I can connect the pump (on a timer again) directly to the indexing valve. On every flood cycle most of the water would go through the indexing valve, and then to a GB and back to the sump, but the other bit of water would go directly to the DWC tanks, then to the fish tank, then split across the GBs, then back to the sump, to keep some flow going through the FT. This is going to require more plumbing than before, but this way I can use a simple timer, pump & IV setup. I still need to estimate if I can get enough flow through the FT and also give the GBs enough time to drain the FT water that has been split to them, before the next one starts to fill. Sorry if this is confusing, it's hard to describe in text.
One issue though might be that one of the cycles I want from the indexing valve would be to feed a few towers. The indexing valve wouldn't need to be at the highest point of the plumbing, would it?
I was also wondering if the indexing valves have an option to connect polypipe directly to them, rather than PVC. I'm hoping to avoid PVC plumbing if I can.
Also, if I want to run my system on constant flood, can I simply take the mechanism out of the IV to open all of the outputs up, or will I need to design in a bypass for that situation?
Thanks!
© 2025 Created by Sylvia Bernstein. Powered by